Specifications
Max. Operating Pressure | Up to 300 psi (20.68 bar) |
Process Temperature Range | Based on fill fluid – Maximum 401°F (205°C), Minimum -157°F (-105°C) |
Communication Protocol | 4-20 mA HART®, WirelessHART®, FOUNDATION™ Fieldbus, PROFIBUS®, 1-5 V Low Power HART® |
Seal System Type | Direct Mount, Tuned-System |
Transmitter Connection | Welded-Repairable |
Process Connection | Flanged: ANSI/ASME, EN/DIN, JIS |
Process Wetted Material | 316L SST, Alloy C-276, Tantalum |
Diagnostics | Basic Diagnostics |
Certifications/Approvals | SIL 2/3 certified to IEC 61508 by an independent 3rd party, NACE®, hazardous location, see full specs for complete list of certifications |
Features
- Designed with a variety of process connections, materials and output protocols to meet diverse application requirements
- Tuned-System Level assembly and direct mounting produce optimal performance for level applications
- SIL 2/3 certified to IEC 61508 (via 3rd party) and prior-use certificate of FMEDA data for safety installations
- Local Operator Interface (LOI) for simple, local commissioning on-site without the use of extra tools or training
- Optimized seal system construction ensures a quality measurement in harsh process conditions