Part Number: YTA610-FA2A4DN/KU25
Model and Suffix Codes
- Model: YTA610 – Temperature Transmitter
- Output signal: -F – Digital communication (FOUNDATION Fieldbus protocol)
- A: Always A
- Sensor input: 2 – Double
- Housing code: A – Aluminium
- Electrical code: 4 – M20 female
- Integral indicator: D – Digital indicator with Local Operating Switch
- Mounting bracket: N – None
- Option Codes:
/KU25: ATEXFieldbus:[Intrinsically safe approval]Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012Certificate No. FM16ATEX0019XII 1 G Ex ia IIC T5…T4 GaAmbient Temperature: -55 to 60?CEnclosure: IP66/IP67 in accordance with only IEC 60529FISCO field deviceEntity Parameters:Supply/Output circuit: Ui=30V, li=300mA, Pi=1.2W, Ci-22nF, Li=0mHSensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10?F, Lo=3.9mHDielectric strength: 500 V a.c.r.m.s., 1 min[+, -, C, 1, 2, 3, 4, 5] to Earth terminal[+, -, C] to [1, 2, 3, 4, 5][Flameproof and Dust Ignition Proof Approval]Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014Certificate: KEMA 07ATEX0130II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70?C/T90?C DbAmbient Temperature for Gas Atmospheres: -40 to 75?C for T6, -40 to 80?C for T5Ambient Temperature for Dust Atmospheres: -30 to 65?C for T70?C, -30 to 80?C for T90?CEnclosure: IP66/IP67Electrical Connection: 1/2 NPT female and M20 female?
NOTE:
- Applicable for Electrical Connection Code 2 and 4.
- Estimated Lead Time: 8 – 10 Weeks
- Shipping Weight: 3 Kg